Apparatus Models and their Parameters

 

1 Apparatus Models and their Parameters
Park model including one amortisseur circuit in the q-axis and the d-axis was used for modeling the generators (the parameters used for the generators themselves are the same as the standard parameters of the Y-method).
These parameters are listed in Table 1.1. Table 1.1 Generator Constants.
1.1 Excitation Models
The following 3 types of the excitation models have been considered.
Rotating type excitation model (LAT = 1)
Thyristor excitation model (LAT = 2)
Thyristor excitation model equipped with DP type PSS (LAT =102)

LAT means ID number of standard AVR type used in CRIEPI’s Y-method. The simplified PSS constants is decided to damp the long term swing (period = 1 – 4 [sec]).
Fig. 1.1 shows the block diagram used and the parameters.
Fig.1.1 Excitation Models

1.2 Governor Models
The following 3 types of the governor models have been considered
Thermal and Nuclear Plants Governor System Model (LPT = 1)
Hydraulic Plants Governor System Model I (LPT = 3)
Hydraulic Plants Governor System Model II (LPT = 4)
LPT means ID number of standard governor type used in CRIEPI’s Y-method. Fig. 2 shows the block diagram and the parameters.
Fig.1.2 Governor Models
The unit of the turbine output is MW base. (When the active power output [MW] is the rated, the turbine output is 1 [pu].)
Fig.1.3 Operation Modes
1.3 Step-Up Transformer
The value of the transformer’s reactance is 0.14 p.u. on machine base. However, the zero impedance is neglected.
1.4 Transmission Lines Models
The transmission lines are represented by the equivalent p circuits. The impedance used is a standard impedance in a 500 kV system of 4 conductors (TACSR 810 mm2 ).
The values of the impedance of a single line, 100 km are given below. The base values are 1000 MVA, 500 kV.
50 Hz System (1000MVA, 500kV base, 1 cct. /100km)
Impedance: Z= r+jX = 0.0046+j0.1068 [p.u.]
Electrical charge capacity: jY/2 = 0.0538 [p.u.]

60 Hz System (1000MVA, 500kV base, 1 cct. /100km)
Impedance: Z= r+jX = 0.0042+j0.1262 [p.u.]
Electrical charge capacity: jY/2 = 0.0610 [p.u.]

The zero impedance of the transmission line was not considered.

1.5 Load Models
The load characteristics were based on past measurements. When the voltage is about 1 p.u., the active power is represented as a constant current. When the voltage is below a certain value, the active power is represented as constant impedance. Under the entire domain of the voltage, the reactive power is represented as constant impedance.
Fig.1.4 Load model (NLT = 2)

However, this load characteristic NLT = 2 is not continuously changed at the load voltage V = 0.7 [pu] .

The following Load characteristic (NLT = 107) is continuously changed between the constant current and the constant impedance characteristic at V = 0.7.
Fig.1.5 Load model (NLT = 107)